The MY600 Digital Insulation Tester has enhanced operation compared to the conventional model, by using a shortened measurement time and color indicating judging function. This is a new concept in insulation testing and includes enhanced communication to a PC or tablet.
- Featuring enhanced measurement response times of 0.5 seconds and new functionallity for PASS/FAIL Judgement and Polarization Index and Dielectirc Absoprtion Ratio testing
- Ability to log up to a 1000 data points to internal memory for offline analysis to a PC
- Automatic LED backlight when working in remote areas with low visibility
- Large voltage generation and resistance measurement ranges to suit a wide variety of insulaiton types
- Basic voltage measurement accuracy of +/- 1% of reading and resistance measurement of +/- 2% of reading with the ability to measure up to 4000 MΩ
- Power off function that minimizes idle time and conserves battery life
- Built-in auto-ranging for improved resolution at lower resistance levels
- IP40 Protection Grade for enhanced ruggedness in harsh enviornments
Main Specifications
Resistance Measurement Accuracy (tolerance): Within 1 year of shipment
Rated Measuring Voltage | 50V | 100V | 125V | 250V | 500V | 1000V |
---|---|---|---|---|---|---|
Maximum Effective Reading | 100 MΩ | 200 MΩ | 250 MΩ | 500 MΩ | 2000 MΩ | 4000 MΩ |
First Effective Measuring Range | 0.100 to 10.00 MΩ | 0.100 to 20.00 MΩ | 0.100 to 25.00 MΩ | 0.100 to 50.00 MΩ | 0.100 to 500 MΩ | 0.100 to 1000 MΩ |
Accuracy at First Effective Measuring Range | ±2% reading ±2 digit | |||||
Second Effective Measuring Range | 10.01 to 100 MΩ | 20.01 to 200.0 MΩ | 25.01 to 250.0 MΩ | 50.1 to 500 MΩ | 501 to 2000 MΩ | 1001 to 4000 MΩ |
Accuracy at Second Effective Measuring Range | ±5% reading | |||||
Accuracy at 0.050 to 0.099 MΩ | ±2% reading ±4 digit | |||||
Accuracy at 0.000 to 0.049 MΩ | ±2% reading ±6 digit |
Other Specifications
Accuracy (tolerance): Within 1 year of shipment
AC Voltage Measurement Range | 2 Vrms to 600 Vrms (45-65 Hz) |
---|---|
DC Voltage Measurement Range | ±(2.0 to 600) Vdc |
AC/DC Voltage Measurement Accuracy | ±1% reading ±4 digit |
Low Resistance Measurement Range | 40.00/400.0/4000 Ω (Auto range) |
Low Resistance Measurement Accuracy | ±2.5% reading ±8 digit (0.20 to 4000 Ω) ±8 digit (0.00 to 0.19 Ω) |
Display | 4000 Counts Digital Display |
Built-in Functions | PI/DAR, PASS/FAIL with indicator, USB communication, Auto LED light |
Measurement Categories | CAT III 600V |
Protection Grade | IP40 |