Hioki’s non-contact voltage detection and measurement technology places efficiency and safety as priority considerations with the goal of protecting customers that need to conduct on-site electrical work as part of renovations and expansions of manufacturing plants and buildings.
The PD3259-50 Digital Phase Detector lets you to measure three-phase voltage and detect phase sequence simultaneously by just clipping onto covered cables, ensuring absolutely no contact with metal parts for maximum safety. CAT IV 600 V
Key Features
• Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
• Available to check the unbalance rate and vector diagram in our free app GENNECT Cross
• World’s first non-metallic contact voltage detection and testing
• Simply clip onto wire insulation • Phase detection check and line-to-line voltage inspection at the same time
• Easy and intuitive phase detection check with backlight and buzzer
• Ideal for work certification photos, offering simultaneous display of phase sequence and 3-phase voltage
Note: Only the voltage value is displayed when measuring a single-phase/3-wire circuit.
Specification
Detection functions | Positive phase, negative phase (Three-phase 3-wire, Three-phase 4-wire), open phase, prediction of ground phase (Three-phase 3-wire) |
---|---|
Measurement parameters | Three-phase AC voltage (line-to-line voltage and voltage to ground), Frequency • Voltage measurement accuracy: ±2.0% rdg. ±8 dgt., • Frequency measurement accuracy: ±0.5% rdg. ±1 dgt., • Response time: 3 s or less, Display update rate: 500 ms |
Measurement targets | Covered cables, Metal portions *Use on shielded cables not supported Three-phase 90.0 to 520.0 V AC (45 to 66 Hz) |
Diameter of measurable conductors | Finished outer diameter: 6 to 30 mm (0.24 to 1.18 in) |
Maximum rated voltage to earth | 600 V AC (CAT IV) |
Environmental protection | Main unit (excluding voltage sensors): IP54 (EN60529) dustproof and waterproof |
Other functions | Hold function, Backlight, Buzzer, Auto power-off, Low battery warning, Drop proof (on concrete, 1 m/ 1 time) |
Power supply | AA alkaline batteries (LR6) ×4, Maximum rated power: 3 VA, Continuous operating time: 5 hours (Backlight off, standby state, Without Z3210) |
Dimensions and mass | 84 mm (3.31 in)W × 146 mm (5.75 in)H × 46 mm (1.81 in)D, 590 g (20.8 oz, including batteries), cord length: 0.5 m (1.64 ft) |
Accessories | AA alkaline batteries (LR6) ×4, Instruction manual ×1, Carrying case C0203 ×1, Color clip (White ×2, red ×2, blue ×2, yellow ×2), Spiral tubes (black ×1) |