Key Features
• Wireless support. Transfers measurements to your smartphone or tablet. (Optional Wireless Adapter Z3210 is necessary)
• Detect minuscule leakage currents with a newly designed sensor. (Core jaw diameter up to φ 40 mm)
• Broad measurement range extending from leakage currents to load currents
• Complies with the performance standard set forth in IEC/EN 61557-13, an international standard on leak clamp meters
• Solve GFCI and RCD problems quickly • Speed up pass/fail judgments with the built-in comparator function CAT IV 300 V CAT III 600 V
specifications:
AC Current range | 6.000 mA, 60.00 mA, 600.0 mA, 6.000 A, 60.00 A, 200.0 A, 6 ranges, True RMS Basic accuracy 45 Hz – 400 Hz: ±1.0% rdg ±5 dgt (6.000 mA to 6.000 A), ±1.5% rdg ±5 dgt (60.00 A, 200.0 A) Basic accuracy 15 Hz – 45 Hz, 400 Hz – 2 kHz: ±2.0% rdg ±5 dgt Defined accuracy range: 0.060 mA to 200.0 A |
---|---|
AC Voltage range | N/A |
Frequency range | 15.0 Hz to 2000 Hz |
Crest factor | 3 (other than 200.0 A range), 1.5 (200.0 A range) |
Filter function | Cut off frequency: 180 Hz ±30 Hz at filter ON (-3 dB) |
Output function | N/A |
Other functions | Max/ Min/ AVG/ PEAK MAX/ PEAK MIN value display, Display value hold and auto hold; Backlight, Auto power save, Buzzer sound, Event count display, Comparator, Simple event recording, Rush current measurement |
Display | Display refresh rate: 5 times/s |
Power supply | AA-size alkaline battery (LR6) × 2; Continuous operating time: 48 hr. (without Z3210 installed), 30 hr. (with Z3210 installed and using wireless communications) |
Core jaw diameter | φ 40 mm (1.57 in.) |
Dimensions and mass | 64 mm (2.52 in) W × 233 mm (9.17 in) H × 37 mm (1.46 in) D, 400 g (14.1 oz.) |
Accessories | Carrying case C0203 × 1, Instruction manual × 1, Operating Precautions × 1, AA-size alkaline battery (LR6) × 2 |