Description:
The Fluke PQ400 Electrical Measurement Window enables the connection of three phase measurement equipment to energized panels, without the need to open the panel door, or wear supplemental personal protective equipment (PPE)1.
Key features
- Reduced risk—Permanently installed voltage and current connections can be accessed without opening the panel door
- Increased efficiency—Quickly connect your logger or analyzer and begin taking measurements faster than ever
- Easy installation—A standard step drill bit and electro-hydraulic hole punch provide the simple means to quickly mount the window in the panel
General specifications | |
---|---|
Maximum voltage between any voltage terminal and earth ground | 1000 V |
Maximum voltage between any current terminal and earth ground | 30 V |
Safety | |
General | IEC 61010-1: pollution degree 2 |
Measurement | IEC 61010-2-030: CAT IV 600 V / CAT III 1000 V |
Dimensions | |
Outside | 148 mm x 187 mm x 23 mm (W x H x D) (148 mm x 370 mm x 19 mm with cover opened) |
Inside | 140 mm x 158 mm x Di (W x H x D) Di = 58 – thickness of panel door in mm |
Supported electrical enclosures | |
Enclosure | UL 50/NEMA environmental type 1 (Type 12 when PQ400 cover is closed) |
Panel thickness | Max. 3.5 mm (10 gauge) |
Environment | |
Operating/storage temperature | -25 °C to 60 °C (-13 °F to 140 °F) |
Humidity | 10 % to 90 % in dependency of temperature according to IEC 60721-3-3 Class 3K6 (modified):-25 °C to 35 °C: 10 % to 90 %, 50°C: max. 35 %, 60°C: max. 23 % |
Altitude | |
Operating | 2,000 m (up to 4000 m derate to CAT II 1000 V, CAT III 600 V, CAT IV 300 V) |
Storage | 12,000 m |
Ingress protection | |
Rating | IEC 60529: IP67 with cover closed, IP50 with cover opened and all connectors attached |
Vibration | IEC 60068-2-6 , MIL-PRF28800F: Random vibration class 2 |
Weight | 2.1 kg (4.6 lb) |
Voltage | |
---|---|
Input | |
Number of inputs | 5 (A/L1, B/L2, C/L3, N, and earth/ground) |
Wire gauge | Solid/flexible: 0.25 mm2 to 1.5 mm2 (AWG 24 to AWG 16) |
Voltage | Max. 1000 V |
Fuse | 2 A 1000 V 1.5 A²s, 10 kA IR (A/L1, B/L2, C/L3, N) |
Output | |
Connectors | 5x 4 mm safety terminals, 3x red for A/L1, B/L2, C/L3, 1x black for N, 1x green for earth/ground |
Load current | Max. 1 A rms |
Current | |
---|---|
Input/output | |
Connectors | 5x 4-pin circular compatible with Fluke 354x FC, 173x, and 174x power and power quality loggers (these loggers can all be power from the measured voltage up to 500V)v |