Product overview: Fluke T6-1000 Electrical Tester.
Measure voltage without test leads:
The Fluke T6-1000 Electrical Tester with FieldSense™ technology lets you quickly, safely take True rms voltage and current measurements without test leads.
Unlike other fork testers that merely detect voltage, the T6-1000 makes actual measurements, without contacting a live, metallic conductor. Just slide the 17.8 mm open fork, the widest in the industry, over a conductor and read simultaneous voltage and current values. Or simultaneous frequency and current values. The open fork works with wires up to AWG 4/0 (120 mm2). Or, you can use the attached test leads to measure voltage DC to 1000 V.
- True rms voltage and current to 200 A AC, 1000 V AC
- Resistance 1 Ω to 100 kΩ
Work on any jobsite:
Make use of the HOLD button to temporarily freeze the reading on the screen so you can keep working with the same measurement up. Plus, the display features large, easy-to-read numbers and a backlight for darker work environments or inside cabinets. The T6-1000 works with the Fluke TPACK ToolPak™ Magnetic Meter Hanger to make it even more convenient.
How FieldSense™ technology works:
FieldSense ™ technology is different than other open fork testers work by interpreting a magnetic field to show AC current. FieldSense™ detects an electrical field that interacts with a T6 reference signal, showing a voltage value on the tester’s display.
Key features:
- Measure voltage to 1000 V AC without test leads
- Simultaneously measure voltage and current
- 17.8 mm open fork is widest in the industry
- Measure up to 200 A on 4/0 wires (120 mm2)
Measurement Specifications | ||||
---|---|---|---|---|
Function | Requires test leads | Range | Resolution | Accuracy[1] |
FieldSense ac voltage true-rms | No | 1000 V | 1 V | ± (3 % + 3 counts) 45 Hz – 66 Hz[2][3] |
FieldSense ac current true-rms | No | 200.0 A | 0.1 A | ± (3% + 3 counts) 45 Hz – 66 Hz |
FieldSense frequency (Hz) | No | 45 Hz – 66 Hz | 1 Hz | ± (1% + 2 counts)[3] |
Volts ac true-rms | Yes | 1000 V | 1 V | ± (1.5% + 2 counts) 45 Hz – 66 Hz |
Volts dc | Yes | 1000 V | 1 V | ± (1% + 2 counts) |
Resistance | Yes | 2000 Ω | 1 Ω | ± (1% + 2 counts) |
Yes | 20.00 kΩ | 0.01 kΩ | ||
Yes | 100.0 kΩ | 0.1 kΩ | ||
Safety | 1000 V CAT III 600 V CAT IV |
General Specifications | ||
---|---|---|
Calibration | 1-year calibration cycle | |
Dimensions | 61.1 x 259.3 x 43.8 mm | |
Jaw opening | 17.8 mm | |
Weight | 0.35 kg (0.78 lb) | |
Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
Altitude | Operating | 2,000 m (6,562 feet) |
Storage | 10,000 m (32,808 feet) | |
Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
0.1 x (specified accuracy) / °C for <18°C or >28 °C | ||
Safety | IEC/EN 61010-1: Pollution Degree 2 | |
Electromagnetic Environment | IEC/EN 61326-1: Portable |